No revocation or modification of this ruling appears in the Customs Bulletin issues read here (Nov 6, 2024 through Nov 18, 2026), where CBP publishes most such actions. That is not confirmation that the ruling is still in effect. Confirm its status with CBP before relying on it (ruling on CBP CROSS).
Key passages, quoted from the ruling
- Accordingly, the applicable subheading for the Tornatech GPX Electric Motor Driven Fire Pump Controller will be 9032.20.0000, Harmonized Tariff Schedule of the United States (HTSUS), which provides for “Automatic regulating or controlling instruments and apparatus; parts and accessories thereof: Manostats.” The general rate of duty will be free.
Ruling text
In your letter dated September 19, 2026, on behalf of your client, Tornatech Inc., you requested a tariff classification ruling. Descriptive literature was provided for our review. The item under consideration is described as the Tornatech GPX Electric Motor Driven Fire Pump Controller, which is an industrial electric motor controller designed to automatically start and stop electric motor-driven fire pumps for the purpose of keeping the water lines pressurized.
The central command and control unit is housed in a heavy-duty steel enclosure and features specialized internal electrical circuitry including a main disconnecting means, an overcurrent circuit breaker, motor contactors for alternating current (AC) motor starting (such as across-the-line or part-winding configurations), and a digital microprocessor control panel. The system is primarily designed to continuously monitor water pressure within the fire sprinkler piping via a built-in pressure transducer.
Upon sensing a pressure drop, indicative of a fire emergency or leak, it automatically sequences the starting mechanism to energize the high-horsepower electric fire-pump motor. Once the leak or fire emergency has concluded and the pressure stabilizes, the GPX will turn off the pump and monitor the situation until there is another drop in pressure. It also integrates manual start/stop mechanisms, visual diagnostic displays, and alarm telemetry links.
Chapter 90 Note 7 states: Instruments and apparatus for automatically controlling the flow, level, pressure or other variables of liquids or gases, or for automatically controlling temperature, whether or not their operation depends on an electrical phenomenon which varies according to the factor to be automatically controlled, which are designed to bring this factor to, and maintain it at, a desired value, stabilized against disturbances, by constantly or periodically measuring its actual value.
The Tornatech FOX controller operates entirely based on an electrical phenomenon that varies directly with the physical factor to be controlled, namely, fluid pressure within the fire main loop. While the panel houses components found in heading 8537 (such as circuit breakers and motor starters), these components do not serve the independent purpose of general electrical distribution.
Rather, they function entirely as the sub-components of an integrated machine whose principal function (per Section XVI Note 3, applicable to Chapter 90 via Note 3) is the automatic regulation of pressure. Additionally, the electric motor driven fire pump controller has all of the components necessary to meet Chapter 90 Note 7.
This includes: A) the measuring device (a 0-500 PSI pressure transducer continuously sensing system side water pressure); B) the control device (ViZiTouch V2.1 embedded control logic, comparing measured pressure to field-adjustable cut-in/cut-out setpoints); and C) the operating device (model specific contactors/starters energizing or de-energizing the dedicated fire pump motor).
The text above is an excerpt. The official ruling, with its letterhead, signature and any attachments, is on CBP CROSS (N365234).