The tariff classification of automatic power factor correction systems from Canada
No revocation or modification of this ruling appears in the Customs Bulletin issues read here (Nov 6, 2024 through Nov 18, 2026), where CBP publishes most such actions. That is not confirmation that the ruling is still in effect. Confirm its status with CBP before relying on it (ruling on CBP CROSS).
Ruling text
In your letter dated October 26, 2026, you requested a tariff classification ruling. Descriptive literature was provided for our review. The merchandise under consideration is described as self-contained automatic power factor correction (APFC) systems for low-voltage industrial and commercial electrical installations.
The systems continuously measure the power factor of the installation and automatically switch capacitor stages into and out of the circuit to hold the power factor at a target value set on its controller. The systems come in three model rating configurations including: 480-2100K-G2-STD 480 V, 2,100 kVAR containing three enclosure sections; 480-1500K-G2-STD 480 V, 1,500 kVAR containing two enclosure sections; and 208-500K-G1C-STD 208 V, 150 kVAR containing one enclosure.
Each system is imported fully assembled, wired and tested. The systems each contain several components. The first is a power factor controller, which measures voltage and current, calculates the power factor, and compares it with the set target and switches capacitor steps to reach it. Additionally, it equalizes wear between steps, counts switching operations, and displays system voltage, current, kW, and power factor.
The second is the current sensor (Rogowski coil), which is installed on the incoming supply, providing the measurement signal to the controller. The third is the capacitor cells, which are arranged in switchable steps. The fourth is the capacitor-duty contactors with early-make contacts and damping resistors that connect and disconnect the capacitor steps on the controller’s command.
The HRC Class J fuses (three per step) contain blown-fuse indication, a surge protection device, 24 V DC power supply, and communication, data-logging, and power-analyzer modules. The status lights (normal, fault, under-compensation, SPD failure) also have an integrated thermal overload alarm. Each enclosure is made of 16-gauge powder-coated steel.
In operation, the systems function within electrical installations containing inductive loads, such as motors, which draw lagging reactive power and reduce the overall power factor. When the monitored power factor falls below a predetermined threshold (typically between 0.90 and 0.95), the system’s controller dynamically switches in the requisite capacitance to offset the reactive power.
Conversely, as the electrical load decreases, the controller disengages the capacitor capacity to prevent system over-compensation. This apparatus does not alter the real power (measured in kilowatts) consumed by the loads; rather, it regulates reactive power and the resultant current drawn from the power supply.
The applicable subheading for the APFC systems will be 9032.89.4000, Harmonized Tariff Schedule of the United States (HTSUS), which provides for “Automatic regulating or controlling instruments and apparatus; parts and accessories thereof: Other instruments and apparatus: Other: Automatic voltage and voltage-current regulators: Other.” The general rate of duty will be 1.7 percent ad valorem. The duties cited above are current as of this ruling’s issuance.
Duty rates are provided for your convenience and are subject to change.